  • Im Serienresonanzexperiment konnte keine automatische Abstimmung des Geräts erreicht werden, da der Resonanzpunkt nicht gefunden werden konnte.

    The series resonance Die Nutzung von UHV-Strom kann vielen Energiearbeitern die Durchführung verschiedener Leistungstests erleichtern.

    32

    Phenomenon:

    The tuning curve is a straight line, and the instrument indicates no resonance point after tuning

    reason:

    Poor grounding of the circuit, incorrect wiring of the testing circuit, and open circuit of the instrument and equipment

    Elimination method:

    1) Check if the grounding device is reliable and if the grounding connection wire is disconnected;

    2) Check the on/off status of the high and low voltage coils of the excitation transformer; (Low voltage winding resistance; high voltage winding resistance at each output end vs high voltage tail)

    3) Check the continuity of each reactor; (Resistance of each winding)

    4) Check the continuity of the voltage divider signal line; (High and low voltage capacity)

    5) Check the continuity of the high and low voltage capacitor arms of the voltage divider; (Core 1 hole, shell 2 holes; 1 hole is disconnected from 2 holes)

    6) The device itself does not have a resonance point for boosting, and it is necessary to check the continuity of the compensation capacitor;

    If all components are normal and there are still no resonance points, please contact the after-sales company and do not disassemble the instrument by yourself!

    Das könnte Ihnen auch gefallen

    • Haben Sie Fragen!

      Zögern Sie nicht, uns jederzeit zu kontaktieren
      Kontaktiere uns
    • Besuchen Sie uns

      Gebäude 6, Optics Valley Optical-Mechanical Industrial Park, 84 Gaoxin 5 Road,
      East Lake New Technology Development Zone, Stadt Wuhan, Provinz Hubei, China

    • Schreiben Sie uns eine E-Mail

      qiao@hvtest.cc

    • Rufen Sie uns an

      +86-15871365102